70
11 Supplement
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
L
2 mm
(0.079
")
0
-2mm
(-0.079
")
15mm
(0.591
"
)
-15mm
(-0.591")
0,35 m
(13.78")
0,2 m
(7.874")
0,2 m
(7.874
")
0,05 m
(1.969
")
1 1
Fig.38:DeviationVEGAFLEX83incableversion(coated)inoil
1 Dead band - no measurement possible in this area
L Probe length
Repeatability ≤ ±1 mm
Variablesinuencingmeasurementaccuracy
Temperature drift - Digital output ±3 mm/10 K relating to the max. measuring range or
max. 10 mm (0.394 in)
Additional deviation through electromag-
netic interference acc. to EN 61326
< ±10 mm (< ±0.394 in)
Inuenceofthesuperimposedgasandpressuretotheaccuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by
high pressure. This eect depends on the superimposed gas or vapour and is especially large at
low temperatures.
The following table shows the resulting deviation for some typical gases and vapours. The specied
values refer to the distance. Positive values mean that the measured distance is too large, negative
values that the measured distance is too small.
Gas phase Temperature Pressure
1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig)
Air 20 °C/68 °F 0.00 % 0.22 % 1.2 %
200 °C/392 °F -0.01 % 0.13 % 0.74 %
400 °C/752 °F -0.02 % 0.08 % 0.52 %
Hydrogen 20 °C/68 °F -0.01 % 0.10 % 0.61 %
200 °C/392 °F -0.02 % 0.05 % 0.37 %
400 °C/752 °F -0.02 % 0.03 % 0.25 %